Basic Principles of Serial Data Transmission
2.8 Configuration data
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
102 Manual, 09/2008, A5E02191071-01
Output by means of message text number (%N)
Use the N display type to start printing message texts stored on the CP 341. The conversion
statement variable contains the number of the message text.
Example: The pressure in the chamber "is falling"
Format
string
= %N %S
Variable 1 = 17 (message text no. 17: The pressure in the chamber ...)
Variable 2 = reference to string (string variable: ... is falling)
Note
Within a message text, all conversion statements except for %N and all control statements
except for "\F" and "\x" are allowed! An explicit width setting of %N limits the printed length of
the referenced message text to the width indicated.
Setting the page number (%P)
Use the P display type to change the page number in the printout.
The CP 341 always begins a printout at page 1. This conversion statement allows you to set
the page number to a specific value. The conversion statement variable contains the page
number to be set.
Example: (Setting the page number to 10)
Format
string
= %P
Variable 1 = 10 (page number: 10)
Note
In the case of the P display type, there must be no further text, conversion statements, or
control statements in the format string. The P display type is not permitted in configured
message texts.