Commissioning
S7-300 Programmable Controller Hardware and Installation
8-18 A5E00105492-01
Event CPU 313 / 314 / 314 IFM (314-5AE10) / 315 / 31x-2 DP /
CPU 31xC
CPU 312 IFM /
314 IFM (314-5AE0x)
Memory contents
after reset
The status of CPU memory space is "0". If a Memory Card
or MMC has been inserted, the user program is transferred
again to main memory.
The user program is
loaded back into the
RAM from the
integrated retentive
EPROM of the CPU.
Data in the diagnostics buffer.
You can read the diagnostic buffer with the PG (see STEP 7 Online Help).
The MPI parameters (MPI address and highest MPI address, transmission rate,
configured MPI addresses of CPs/FMs in an S7-300).
What's left?
The contents of the operating hours counter (not for CPU 312 IFM).
Special feature: MPI parameters
MPI parameters hold a special position when memory is reset. The table below
describes MPI parameters remaining valid after memory reset.
Memory reset ... MPI parameters
with inserted Memory Card (MMC)
With integrated FEPROM load memory
(CPU 312 IFM / 314 IFM (314-5AE0x)
... located on the memory card or on the
integrated FEPROM of the CPU are valid. If
this location does not contain parameter
data (SDB), the previously set parameters
stay valid.
Without Memory Card (MMC) ... are retained and valid.
CPU 312 IFM and 314 IFM: Erasing the integrated EPROM
If you wish to erase the contents of the integrated EPROM, proceed as follows:
1. Use menu command View > online to open the online window for viewing an
open project
or
open the window Available nodes with a click on the Available nodes
toolbar button or select the menu command PLC > Show available nodes .
2. Select the MPI number of the target CPU (double-click).
3. Select the Modules container.
4. Select the menu item Edit > Select all.
5. Then select the menu command File > Delete or press the DEL key. This
deletes all selected blocks from target memory.
6. Select the MPI number of the target CPU.
7. Select the menu command PLC > Copy RAM to ROM.
These commands delete all blocks online and overwrite the EPROM with the blank
contents of the RAM.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)