Commissioning
S7-300 Programmable Controller Hardware and Installation
8-30 A5E00105492-01
Commissioning
Commission CPU 31x-2 DP/31xC-2 DP as DP slave in the PROFIBUS subnet as
follows:
1. Switch on power, but hold the CPU in STOP mode.
2. First, switch on all other DP masters/slaves.
3. Now switch the CPU to RUN mode.
Startup of CPU 31x-2 DP/31xC-2 DP as DP slave
When the CPU 31x-2 DP/31xC-2 DP is switched to RUN, two independent
operating mode transitions are executed:
The CPU switches from STOP to RUN mode.
At the PROFIBUS-DP interface the CPU starts data transfer with the DP
master.
Recognizing the Operating State of the DP Master (Event Recognition)
The table below shows how CPU 31x-2 DP/31xC-2 DP as DP slave recognizes
operating mode transitions or data exchange interrupts.
Table 8-9 Event recognition by CPUs 31x-2 DP/31xC-2 DP as DP slave
Event What happens in the DP slave?
Bus failure interrupt
(short-circuit,
connector
unplugged)
Call of OB86 with the message Station failure
(coming event; diagnostic address of the DP slave, assigned to
the DP slave)
with I/O access: Call of OB122
(I/O access error)
DP master.
RUN STOP
Call of OB82 with the message Module error
(coming event; diagnostic address of the DP slave, assigned to
the DP slave; Variable OB82_MDL_STOP=1)
DP master
STOP RUN
Call of OB82 with the message Module OK
(outgoing event; diagnostic address of the DP slave, assigned to
the DP slave; Variable OB82_MDL_STOP=0)
Tip:
When commissioning the CPU as DP slave, always program OB 82 and 86. This
helps you to recognize and evaluate the respective operating states or data
exchange errors.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals