Testing functions, Diagnostics and Fault Elimination
S7-300 Programmable Controller Hardware and Installation
10-4 A5E00105492-01
10.3 Overview: Diagnostics
Introduction
System errors can occur especially in the Commissioning phase. Tracking these
errors might be a time-consuming effort, since they can occur likewise on hardware
and on software side. Here, the multitude of testing functions ensures
commissioning without problems.
Errors duringoperation are almost always a result of faults or damage to the
hardware.
Types of Error
Errors the S7 CPUs can recognize and to which you can react with the help of
organization blocks (OBs) can be split into the following two categories:
Synchronous errors: Errors you can relate to a specific point in the user
program (e.g. error when accessing a peripheral module).
Asynchronous errors: Errors you can not relate to a specific point in the user
program (e.g. cycle time exceeded, module error).
Error Handling
Programming with foresight and, above all, knowledge and proper handling of
diagnostic tools puts you into an advantageous position in error situations:
You can reduce the effects of errors.
It makes it easier for you to locate errors (e.g. by programming error OBs).
You can limit downtimes.
Diagnostics with LED display
SIMATIC S7 hardware offers diagnostics with LEDs.
These LEDs are implemented in three colors:
Green LEDs report regular operation (e.g. supply voltage is applied).
Yellow LEDs indicate special operating states (e.g. "Force" is active).
Red LEDs report errors (e.g. bus error)
A flashing LED also indicates a special event (e.g. memory reset).
Cross-reference
Notes on diagnostics with LEDs are found in the Chapter below.
Notes on diagnostics of I/O modules capable of diagnostics are found in the
respective Manual.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals