Basic functions
4.2 Homing
Connection of the SINAMICS S120 to the Technology CPU
Product Information, 09/2011, A5E00480378-04
117
4. In the "Ext. zero mark input" box, enter the address of the integrated inputs of the
Technology CPU from HW Config, for example PI66.0.
5. Enter meaningful values in the "Approach velocity", "Entry velocity",
and "Reduced velocity" input boxes.
Note
Note that only negative edges are permitted for the positive travel direction, and only
positive edges are permitted for the negative travel direction, which means that the same
cam side is always used. In the dialog box for the "Homing" function, select the
"Data transfer from the drive" button to preassign the input fields with the data set for
SINAMICS. If you then change the settings, the necessary settings in SINAMICS will be
displayed in an information box.
This completes the configuration of the technological part of the homing function in
S7T Config.
Creating the S7 user program
Use the Technology Object Manager (TOM) to create a technology data block (TO-DB),
which is assigned to the homing output cam technology object. The technology data block
(TO-DB) allows the functions on the associated technology object to be executed using the
provided FBs. For the homing, use the FB403 MC_Home function block in your S7 program.
4.2.5 Example: Active homing using only an encoder zero mark
Introduction
The simplest form of homing is the homing only with encoder zero mark. It is used,
for example, for axes whose encoder has only one zero mark in the complete travel area of
the axis. This homing command causes the axis to travel to the zero mark. Once the axis
detects the zero mark, the home position offset is applied at homing entry velocity.
The axis position now has the value specified in the home position coordinate.
Operational sequence
No BERO signal is required. The position is accepted at the next zero mark of the encoder.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals