Commissioning
3.4 Configuring the drive components
Connection of the SINAMICS S120 to the Technology CPU
Product Information, 09/2011, A5E00480378-04
61
8. For Smart Line Modules without DRIVE-CLiQ interface, a message appears with
information on the hardware wiring of the ready signals between infeed and the drive.
Read this information and confirm the message with "OK".
Note
For SLM without DRIVE-CLIQ, the hardware wiring of the ready signal for the infeed can
take place either via the digital inputs of the CU 320 control unit or via the additional
digital inputs of the TB 30 terminal board.
The appropriate input of the signal is then used for the subsequent internal wiring
of the BICO signals.