Counter module FM 450-1
Manual, 02/2014, A5E03648739-02
103
Assignment of the DB
10
10.1
Assignment of the DB
DB for the FC°CNT_CTRL
All data associated with a channel of the module are located in the DB of FC CNT_CTRL.
The data structure and the length of the DB is determined by the variable declaration in
FC CNT_CTRL. Prior to configuring the module, the DB must have the following valid data
assigned to it (see section "Program (Page 45)"):
Module address (address 6.0)
Channel starting address (address 8.0)
User data length (address 12.0)
The DB was generated from the UDT 1 as a data block with associated, user-specific data
type (see section "Program (Page 45)"). The DB assignments resulting from this are shown
below.
Table 10- 1 Assignment of the DB
Address
Variable
Data type
Initial value
Comment
0.0
AR1_BUFFER
DWORD
DW#16#0
AR1 buffer
4.0
FP
BYTE
B#16#0
Flag byte
5.0
RESERVED
BYTE
B#16#0
Reserved
6.0
MOD_ADR
WORD
W#16#0
Module address
8.0
CH_ADR
DWORD
DW#16#0
Channel address
12.0
U_D_LGTH
BYTE
B#16#0
User data length
13.0
A_BYTE_0
BYTE
B#16#0
Reserved
14.0
LOAD_VAL
1
DINT
L#0
New load value (write user)
18.0
CMP_V1
1
DINT
L#0
New comparison value 1 (write user)
22.0
CMP_V2
1
DINT
L#0
New comparison value 2 (write user)
26.0
A_BIT0_0
BOOL
FALSE
Reserved
26.1
TFB
BOOL
FALSE
Test enabled
26.2
A_BIT0_2
BOOL
FALSE
Reserved
26.3
A_BIT0_3
BOOL
FALSE
Reserved
26.4
A_BIT0_4
BOOL
FALSE
Reserved
26.5
A_BIT0_5
BOOL
FALSE
Reserved
26.6
A_BIT0_6
BOOL
FALSE
Reserved
26.7 A_BIT0_7 BOOL FALSE Reserved
27.0
ENSET_UP
1
BOOL
FALSE
Enable setting in up direction (write user)
27.1
ENSET_DN
1
BOOL
FALSE
Enable setting in down direction (write user)