SIMEAS-Hub English
E50417-K1074-C299-A1 39
Connection Hints
Auxiliary Voltage
Direct Cable Connection: Solid or stranded conductor with connector sleeve for conductor
cross-sections from 0.5 mm
2
to 2.5 mm
2
, corresponding to AWG 22 to 12. The rated voltage
of the connecting cables must be at least 300 V AC. Tightening Torque: min 0.5 Nm
The maximum rated current of the device is 0.5 A. To ensure proper selectivity in the fusing
sequence, the power supply line is to be equipped with a minimum 2 A circuit breaker (the
maximum value depends on the wiring of the cabinet). The circuit breaker must be installed
close to the device. The circuit breaker must be marked as a switch for the device.
Ethernet Connection
The rated voltage of the Ethernet connections (10Base-T) must be 300 V AC minimum.
Fibre Optic
You have to comply with the permissible bending radii of the fibre optic cable. In other cases,
you may destroy the optical fibres.
Warning
Do not look directly into the fibre-optic elements or cables!