53
2.8 Measured Values
Measured values
Measuring
path
1
Menu Tolerances
2
Voltage
L1-N, L2-N,
L3-N
d a h
±0.2 %
Voltage
L1-L2, L2-L3,
L3-L1, Σ
3
d a h
±0.2 %
Current
L1, L2, L3, N,
Σ
3
d a h
±0.2 %
Active power P
+ import, - export
L1, L2, L3, Σ
d a h
±0.5 %
Reactive power Q
+ cap, - ind
L1, L2, L3, Σ
d a h
±0.5 %
Apparent power S
L1, L2, L3, Σ
d a h
±0.5 %
Power factor |cosϕ|
4
L1, L2, L3, Σ
d a h
±0.5 %
Active power factor
cosϕ
4
L1, L2, L3, Σ
d a h
±0.5 %
Phase angle
4
L1, L2, L3, Σ
d a h
±
Frequency
5
L1-N
d a h
±10 mHz
Active energy import
L1, L2, L3, Σ
d a
±0.5 %
Active energy export
L1, L2, L3, Σ
d a
±0.5 %
Active energy absolute
L1, L2, L3, Σ
d a
±0.5 %
Active energy sum
Σ
d a
±0.5 %
Reactive energy cap
L1, L2, L3, Σ
d a
±0.5 %
Reactive energy ind
L1, L2, L3, Σ
d a
±0.5 %
Reactive energy absolute
L1, L2, L3, Σ
d a
±0.5 %