Parameters and Properties
17
Power Meter, SIMEAS P 7KG7750/55, Manual
E50417-B1076-C375-A3, Release 01.2009
At devices with integrated display the following bus specific parameters can be set by
selection of the menu “>settings” - “>basic settings” - “>interface”, e.g.:
Fig. 2-2 Screen “>interface”
After selection of "> IEC 103 settings" the screen shown in Fig. 2-2 appears. Here you
can set the "MV range.." as well as transmission of "Harmonics.." and "Counters...".
Fig. 2-3 Sub-screen “IEC 103 settings“ from Fig. 2-2
2.1.2 IEC 60870-5-103 Settings
Bus address Permissible bus addresses are in the range between 1 and 254.
Baud rate The following values for transmission speed are supported:
• 9600 bit/s,
• 19200 bit/s and
• 38400 bit/s.
Parity Parity is adjustable to none, even or odd parity bit (N, E, O). The predefined parity acc.
to IEC 60870-5-103 specification is: E (even).
Note:
The screen is valid from firmware
version 4.10.
*bus address:112
*baudrate: 19200Bd
*parity: E
*protocol: IEC 103
>IEC 103 settings
<ok
<cancel
*MV range: 240%
*Harmonics: no
*Counters: no
<ok
<cancel
Note:
The screen is valid from firmware
version 4.10.
Note:
During the baud rate selection for IEC 60870-5-103 via “SIMEAS P Parameterization”
or via display the complete range from 300 bit/s to 115200 bit/s is offered.
But only 9600 bit/s to 38400 bit/s are permitted for IEC 60870-5-103.