Data Mapping
25
Power Meter, SIMEAS P 7KG7750/55, Manual
E50417-B1076-C375-A3, Release 01.2009
18 Qb Reactive Power (B) I
(nom.)
* V
L-N (nom.)
130 152 no 9 3
19 Qc Reactive Power (C) I
(nom.)
* V
L-N (nom.)
130 152 no 9 4
20 Q Reactive Power 3 * I
(nom.)
* V
L-N (nom.)
130 148 yes 9 8
21 Sa Apparent Power (A) I
(nom.)
* V
L-N (nom.)
130 150 no 9 3
22 Sb Apparent Power (B) I
(nom.)
* V
L-N (nom.)
130 152 no 9 5
23 Sc Apparent Power (C) I
(nom.)
* V
L-N (nom.)
130 152 no 9 6
24 S Apparent Power 3 * I
(nom.)
* V
L-N (nom.)
130 151 no 9 5
25 cos φ (a) cos φ (A) 1 130 150 no 9 4
26 cos φ (b) cos φ (B) 1 130 152 no 9 7
27 cos φ (c) cos φ (C) 1 130 152 no 9 8
28 cos φ cos φ 1 130 151 no 9 6
29 PFa Power Factor (A) 1 130 150 no 9 5
30 PFb Power Factor (B) 1 130 152 no 9 9
31 PFc Power Factor (C) 1 130 152 no 9 10
32 PF Power Factor 1 130 151 no 9 7
33 PHIa Phase Angle (A) 180° 130 150 no 9 6
34 PHIb Phase Angle (B) 180° 130 152 no 9 11
35 PHIc Phase Angle (C) 180° 130 152 no 9 12
36 PHI Phase Angle 180° 130 151 no 9 8
37 Freq System Frequency 5 Hz deviation 130 148 yes 9 9
38 ASymV Asymmetrical Voltage 100 % 130 152 no 9 13
39 ASymI Asymmetrical Current 100 % 130 152 no 9 14
40 THD Van THD Voltage (A-N) 100 % 130 150 no 9 7
41 THD Vbn THD Voltage (B-N) 100 % 130 152 no 9 15
42 THD Vcn THD Voltage (C-N) 100 % 130 152 no 9 16
43 THD Ia THD Current (A) 100 % 130 150 no 9 8
44 THD Ib THD Current (B) 100 % 130 152 no 9 17
45 THD Ic THD Current (C) 100 % 130 152 no 9 18