Data Mapping
28
Power Meter, SIMEAS P 7KG7750/55, Manual
E50417-B1076-C375-A3, Release 01.2009
cos φ The Power Factor cos φ is shown at the device display with
a sign which indicates demand or supply power and
an inductive or capacitive marking.
Example for inductive load and delivered power:
cos φ -1.000 ind
In the cos
φ values which are transmitted via IEC 60870-5-103 only the capacitive/
inductive information is contained using the sign of the value:
negative cos
φ: capacitive
positive cos
φ: inductive.
For the above shown example, the positive 100 % value is transmitted.
3.1.2 Measured Value Telegrams
The measured values of the SIMEAS P50 device are transmitted via IEC 60870-5-103
using seven different telegrams.
Depending on the selected Network type (ref. to Figure 3-1), the parameters to the
transmisson of the harmonics (see chapter 2.1.2) and the assembled I/O modules
either all or only a selected number of these telegrams are sent to the IEC 60870-5-
103 master on request of class 2 data.
Please refer to chapter 3.1.2.9 for more information about the relation of the selected
parameters and the transmitted telegrams.
The measurands telegrams are defined as follows (see next sections):
Note (valid for version 4.10 and higher):
In the case of overflow:
the overflow flag is set,
the measured value is set to its maximum positive or maximum negative value
respectively.