16.1 Technical Data of the SIMEAS R-PMU
253Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Surge IEC 61000-4-5
extended as per customer requirements
Power supply, control and
communications lines Common mode 4 kV,
Differential mode 2 kV (extended 4 kV)
Damped oscillation IEC 61000-4-18; EN 61000-4-18
Damped oscillation Test level 3,
Common mode 2.5 kV
Differential mode 1 kV
Repetition rate 100 kHz and 1 MHz
Voltage dips and
short interruptions IEC 61000-4-11; EN 61000-4-11
IEC 60255-11
Short interruption 100 % to 0 % for 50 ms
Short interruption 100 % to 50 % for 100 ms
Voltage fluctuations IEC 61000-4-11; EN 61000-4-11
AC/DC power supply unit to 80 %, 120 % permanently,
to 40 %, dynamic 2 s, operation 2 s
to 0 %, dynamic 2 s, operation 1 s
Voltage interruptions IEC 61000-4-11; EN 61000-4-11
AC power supply unit to 0 % for 5 s with 50 Hz / 60 Hz ±5 %
switch OFF and automatic restart
Voltage dips IEC 61000-4-11; EN 61000-4-11
AC power supply unit to 0 % for 10 ms
to 40 % for 100 ms
to 70 % for 200 ms with 50 Hz / 60 Hz ±5 %
Function not affected
Interference emission IEC/EN 61000-6-4
Interference field strength EN55011/CISPR11
Class A
Radio interference voltage EN55011/CISPR11
Class A
Harmonics
AC supply voltage IEC 61000-3-2; EN 61000-3-2
AC power supply unit Class A