Averaging time power and frequency recorder
The averaging time of the power and frequency recorder must always be < 5 periods.
Frequency triggering of the power and frequency recorder
Frequency triggering is only possible when the voltage input signal of a VDAU or VCDAU is
at least 20 V
rms
(applies to both 110 V and 220 V input).
Missing entries in the log file on February 28th
If log messages are selected on February 28th of the same day, these messages will not be
transferred. By repeating the selection next day or later the messages will be transferred cor-
rectly.
Auto polling in OSCOP P automatic mode
Minimum time between the polling for records must not be less than 5 minutes.
OSCOP P module Transfer: Configuration --> Automatic mode --> Sequential control -->
Select device --> General --> Minimum time between intervals.
Function "Automatic time setting" in OSCOP P automatic mode (DAKON)
The cycle time of the function "Automatic time setting" must not be less than 20 minutes. Do
not activate this function for SIMEAS R synchronized via a Sync-Box. "Automatic time set-
ting" is only available if OSCOP P runs in DAKON mode.
OSCOP P module Transfer:
Configuration --> Automatic mode --> Synchronization --> Cycle time.
ISDN terminal adapter
When using an ISDN terminal adapter connected to SIMEAS R, configure the modem type
as HAYES, not as ISDN in OSCOP P < V6.60.
Note
No log messages will be lost!