7.1 Phasor Measurement Unit (PMU)
59Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
The tables below give an overview of the data rates of the SIMEAS R-PMU depending on the
device configuration and the reporting rate with UDP and TCP communication via LAN.
Table 7-4 UDP transmission via LAN:
Data transfer rate depending on the configuration and reporting rate in kbit/s,
data format 16 bit integer
Configuration Type Reporting rate (Hz)
10 12 15 20 25 30 50 60
1 AC DAU Positive-sequence system 5 6 7 9 12 14 23 28
1 AC DAU Phasors 7 8 101316203339
2 AC DAUs Positive-sequence system 6 7 9 12 15 18 30 36
2 AC DAUs Phasors 1012151924294858
4 AC DAUs Positive-sequence system 8 10 13 17 21 25 42 51
4 AC DAUs Phasors 1619243240488096
1 DDAU Process values 5 6 8 1113162732
2 DDAUs Process values 7 9 11 14 18 22 36 43
1 BDAU Binary values 4 5 6 8 11 13 21 25
2 AC DAUs
2 DDAUs
Positive-sequence system/
process values
11 13 16 22 27 33 55 66
2 AC DAUs
1 DDAU
1 BDAU
Phasors /
process values /
binary values
12 15 19 25 31 37 62 74