SINUMERIK 840C / SIMODRIVE 611–D (DA)
100406 V.24: ASCII string too long
Serial communication via V.24
Transmission is aborted.
Line in source file is too long; the maximum permissible length is 255 ASCII characters.
Check the source file.
Alarm from SW 6.3
100407 V.24: Invalid path
Serial communication via V.24
The file is not transferred
The stated file path is incorrect
Correct the path
Alarm from SW 6.3
100408 V24: no write access
Serial communication via V.24
The file is not transferred
An attempt was made to write a write–protected file
Remove write access rights
Alarm from SW 6.3
100410 V.24: no free memory available
Serial communication via V.24
The file is not transferred.
Memory of hard disk is exhausted.
Delete files and directories that are no longer required.
Alarm from SW 6.3
100411 V.24: invalid number of digits
Serial communication via V.24: read in via punched tape
The file is not transferred
The syntax of the file being transferred is incorrect
Correct the file name
Alarm from SW 6.3
100412 V.24: object type unknown
Serial communication via V.24: punched tape format
The file is not transferred
An unknown object type was discovered
Correct the data type (correct syntax must be observed, e.g. MPF, SPF, TEA1 ...)
Alarm from SW 6.3
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
Scan
Effect
Explanation
Remedy
Note
1 Alarms
1.5.1 Alarm description
01/99