EasyManua.ls Logo

Siemens SIMODRIVE 611-D - Page 475

Siemens SIMODRIVE 611-D
1154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
More user manuals on ManualsBase.com
7 Drive Machine Data (SIMODRIVE Drive MD) 04.96
7.2.2 FDD MD (data description - SW 3)
Bandwidth current setpoint filter 1
1211
Default value Lower input limit Upper input limit Units
500 0 1 000 Hz
Active
at once
Input of 3dB bandwidth for current setpoint filter 1 (band-stop). The filter is activated in
machine data MD 1200 and MD 1201.
Note:
When 0 is entered for the bandwidth, the filter is parameterized as a proportional element with
a gain of 1.
Block frequency current setpoint filter 2
1213
Default value Lower input limit Upper input limit Units
3 500.0 1 7 999.0 Hz
Active
at once
Input of block frequency for current setpoint filter 2 (band-stop). When block frequencies of <
10 Hz are input, the filter is deactivated (proportional element with a gain of 1). The filter is
activated via machine data MD 1200 and MD 1201.
Note:
The maximum block frequency input value is limited by the sampling frequency of the control
(MD 1000) (parameterization error).
1 1
MD 1213 < ––––––––––––– = –––––––––
2 x MD 1000 2 x T
sampl.
MD 1000 = T
sampl.
=
62.5 µs
125.0 µs
=> MD 1213 <
8000 Hz
4000 Hz
7–60 © Siemens AG 1992 All Rights Reserved 6FC5197- AA50
SINUMERIK 840C (IA)

Table of Contents

Other manuals for Siemens SIMODRIVE 611-D

Related product manuals