02.00 Faults / Alarms
SIEMENS AG 6RX1700-0AD76 10-21
SIMOREG DC Master Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
F064 Watchdog timer has initiated a reset
(active in all operating states)
An internal microprocessor hardware counter monitors whether the program for calculating the firing pulses runs at least once
every 14 ms (program is executed on average every 2.7 to 3.3 ms). If this is not the case, the counter initiates a reset, Fo64 is
then displayed.
Possible fault causes
A7001 electronics board is defective
Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield
connections)
F065 Illegal microprocessor status
(active in all operating states)
An internal microprocessor hardware function monitors the microprocessor for illegal operating states.
Possible fault causes
A7001 electronics board is defective
Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield
connections)
F067 Converter cooling faulty
(active in operating states of o13)
The heatsink temperature monitoring function is activated 6s after connection of the electronics supply.
(The current heat sink temperature is indicated at parameter r013 and on connector K050)
Fault value: r047 Index 002 to 016:
1 Heatsink temperature > 95°C i002 Measured heatsink temperature (16384 .. 100°C)
2 Heatsink temperature sensor is defective i003 Measured ADC value
3 Converter fan is defective
F068 Analog measuring channel faulty (main setpoint, main actual value or analog select input)
(active in all operating states)
Hardware monitoring of measuring circuits
Possible fault causes
A7001 module defective
Measuring circuit saturated (input voltage at terminals 4 and 5 or 6 and 7 higher than approx. 11.3V)
Fault value:
1 Measuring channel for main setpoint / analog select input 1 faulty (terminals 4 and 5)
2 Measuring channel for main actual value faulty (terminals 103 and 104)
3 Measuring channel for analog select input 1 faulty (terminals 6 and 7)
F069 MLFB data are faulty
(active in all operating states)
Possible fault causes
Excessive EMC-related interference is present
(e.g. due to unprotected contactors, unscreened cables, loose shield connections)
A7009 backplane wiring assembly is defective
Fault value: r047 Index 002 to 016:
1 MLFB code number (r070) = MLFB code number (r070)
is illegal
i002 Incorrect MLFB code number
2 MLFB data checksum error -
3 Works number checksum error -
4 Number of words of MLFB data is incorrect -