Parameter list 02.00
11-94 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U177
(2177)
*
S00
Source for input signal and limits for limiter 2 FB 66
Output = connector K9170
i001: Input signal
i002: Positive limiting value (L+)
i003: Negative limiting value (L-)
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 3
FS=
i001: 0
i002: 9168
i003: 9169
Type: L2
P052 = 3
P051 = 40
Offline
U178
(2178)
S00
Limit value for limiter FB 66
Applied to connector K9168
-199.99 to 199.99
[%]
0.01%
Ind: None
FS=100.00
Type: I2
P052 = 3
P051 = 40
Offline
U179
(2179)
*
S00
Source for input signal and limits for limiter 3 FB 67
Output = connector K9173
i001: Input signal
i002: Positive limiting value (L+)
i003: Negative limiting value (L-)
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 3
FS=
i001: 0
i002: 9171
i003: 9172
Type: L2
P052 = 3
P051 = 40
Offline
U180
(2180)
S00
Limit value for limiter FB 67
Applied to connector K9171
-199.99 to 199.99
[%]
0.01%
Ind: None
FS=100.00
Type: I2
P052 = 3
P051 = 40
Offline
Limit-value monitors with filtering
U185
(2185)
*
S00
Source for input signal (A) and operating point (B) for FB 70
1
st
limit-value monitor with filtering
i001: Input signal
i002: Operating point
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=
i001: 0
i002: 9181
Type: L2
P052 = 3
P051 = 40
Offline
U186
(2186)
S00
Settable operating point for limit-value monitor FB 70
Applied to connector K9181
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Offline
U187
(2187)
S00
Filter time for 1
st
limit-value monitor with filtering FB 70
0 to 10000
[ms]
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
U188
(2188)
S00
Hysteresis for 1
st
limit-value monitor with filtering FB 70
0.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Offline
U189
(2189)
*
S00
Source for input signal (A) and operating point (B) for FB 71
2
nd
limit-value monitor with filtering
i001: Input signal
i002: Operating point
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=
i001: 0
i002: 9183
Type: L2
P052 = 3
P051 = 40
Offline
U190
(2190)
S00
Settable operating point for limit-value monitor FB 71
Applied to connector K9183
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Offline
U191
(2191)
S00
Filter time for 2
nd
limit-value monitor with filtering FB 71
0 to 10000
[ms]
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline