Parameter list 02.00
11-128 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U664
(2664)
*
Source for switchover to setpoint step S4 [SW 1.7 and later]
0 = Binector B0000
1 = Binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
off-line
U665
(2665)
Setpoint for setpoint step S1 [SW 1.7 and later]
0.00 to 110.00
[%]
0.01%
Ind: None
FS=10.00
Type: O2
P052 = 3
P051 = 40
on-line
U666
(2666)
Setpoint for setpoint step S2 [SW 1.7 and later]
0.00 to 110.00
[%]
0.01%
Ind: None
FS=25,00
Type: O2
P052 = 3
P051 = 40
on-line
U667
(2667)
Setpoint for setpoint step S3 [SW 1.7 and later]
0.00 to 110.00
[%]
0.01%
Ind: None
FS=40.00
Type: O2
P052 = 3
P051 = 40
on-line
U668
(2668)
Setpoint for setpoint step S4 [SW 1.7 and later]
0.00 to 110.00
[%]
0.01%
Ind: None
FS=100.00
Type: O2
P052 = 3
P051 = 40
on-line
11.71 Configuration of supplementary boards in board locations 2 and 3
U710
(2710)
*
Initialize link to supplementary boards
i001 Initialization of 1
st
communications board (in slot with lower ID
letter)
i002 Initialization of 2
nd
communications board (in slot with higher ID
letter
Settings:
0 The link to supplementary boards is re-initialized. After the
configuration parameters for supplementary boards have been
changed, U710 must be set to 0 so that the new settings can
take effect.
The parameter is then set automatically to 1.
Note: Data transmission is interrupted while initialization is in
progress.
1 Deactivated
0 to 1
1
Ind: 2
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
U711
(2711)
*
Communications board parameter 1 (CB parameter 1)
See documentation for installed COM BOARD.
This parameter is relevant only if a communications board is installed. The
validity of the setting is monitored by the CB. If the CB rejects the setting,
fault message F080 is displayed with fault value 5
Index 1 is used to parameterize the 1
st
CB (including CB behind TB) and
index 2 to parameterize the 2
nd
CB.
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U712
(2712)
*
Communications board parameter 2 (CB parameter 2)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U713
(2713)
*
Communications board parameter 3 (CB parameter 3)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U714
(2714)
*
Communications board parameter 4 (CB parameter 4)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U715
(2715)
*
Communications board parameter 5 (CB parameter 5)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U716
(2716)
*
Communications board parameter 6 (CB parameter 6)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U717
(2717)
*
Communications board parameter 7 (CB parameter 7)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U718
(2718)
*
Communication Board Parameter 8 (CB-Parameter 8)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online