02.00 Parameter list
SIEMENS AG 6RX1700-0AD76 11-129
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U719
(2719)
*
Communications board parameter 9 (CB parameter 9)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U720
(2720)
*
Communications board parameter 10 (CB parameter 10)
See U711
0 to 65535
1
Ind: 2
FS=0
Type: O2
P052 = 3
Online
U721
(2721)
*
Communications board parameter 11 (CB parameter 11)
See U711
0 to 65535
1
Ind: 10
FS=0
Type: O2
P052 = 3
Online
U722
(2722)
*
Telegram failure time for CB and TB
i001: Telegram failure time for board location 2
i002: Telegram failure time for board location 3
Settings:
0 No time monitoring, must be parameterized for sporadic
(acyclic) telegrams
1...65000 Permissible time interval between two process data
exchange operations before a fault message is output.
Fault message F082 is displayed if no process data are exchanged with the
supplementary board within this delay period. The monitoring function is
implemented within a 20 ms cycle. For this reason, only setting values
which constitute a multiple of 20 ms are meaningful.
Note:
The telegram monitoring function is active
from the receipt of the first error-free telegram after connection of the
electronics power supply
from the receipt of the first error-free telegram after the telegram
monitor has responded (i.e. monitoring timeout).
0 to 65000
[ms]
1ms
Ind: 2
FS=0
Type: O2
P052 = 3
Online
n732
(2732)
CB/TB diagnostics
Diagnostic information about an installed communications board (CB) or
technology board (TB).
i001 - i032: 1. CB/TB (lower slot ID letter)
i033 - i064: 2. CB (higher slot ID letter)
i065, i066: 1. CB/TB (internal diagnostic data)
i067, i068: 2. CB (internal diagnostic data)
For detailed information, please refer to operating instructions of relevant
CB or TB.
Ind: 68
Type: O2
P052 = 3
n733
(2733)
CB/TB receive data
Display of control words and setpoints (process data) that are transferred to
the basic converter from a communications board (CB) or technology board
(TB).
i001: 1
st
process data word from 1
st
CB/TB
...
i016 16
th
process data word from 1
st
CB/TB
i017: 1
st
process data word from 2
nd
CB
...
i032: 16
th
process data word from 2
nd
CB
0000 to FFFF H
1
Ind: 32
Type: O2
P052 = 3