Parameter list 02.00
11-130 SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
U734
(2734)
*
Transmit data for first CB/TB (lower slot ID letter)
Selection of connectors whose contents must be injected as transmit data
to the first communications board (CB) or technology board (TB).
0 = connector K0000
1 = connector K0001
etc.
This parameter not only defines the transmit data, but also their position in
the transmit telegram.
i001: Word 1 in PZD section of telegram
i002: Word 2 in PZD section of telegram
...
i016: Word 16 in PZD section of telegram
Status word 1 (K0032) should be linked to word 1.
All connector
numbers
1
Ind: 16
FS=0
Type: L2
P052 = 3
Online
n735
(2735)
Display of transmit data to CB/TB
i001: 1
st
process data word to 1
st
CB or TB
...
i016 16
th
process data word to 1
st
CB or TB
i017: 1
st
process data word to 2
nd
CB
...
i032: 16
th
process data word to 2
nd
CB
0000 to FFFF H
1
Ind: 32
Type: O2
P052 = 3
U736
(2736)
*
Transmit data for second CB (higher slot letter)
Selection of connectors whose contents must be injected as transmit data
to a communications board (CB) with a higher slot ID letter.
0 = connector K0000
1 = connector K0001
etc.
This parameter not only defines the transmit data, but also their position in
the transmit telegram.
i001: Word 1 in PZD section of telegram
i002: Word 2 in PZD section of telegram
...
i016: Word 16 in PZD section of telegram
Status word 1 (K0032) should be linked to word 1.
All connector
numbers
1
Ind: 16
FS=0
Type: L2
P052 = 3
Online
n738
(2738)
Display of PKW job from supplementary boards in locations 2 and 3
i001: 1
st
word of PKW job from 1
st
CB
...
i004 4
th
word of PKW job from 1
st
CB
i005: 1
st
word of PKW job from location 2
nd
CB
...
i008 4
th
word of PKW job from 2
nd
CB
i009: 1
st
word of PKW job from TB
...
i012: 4
th
word of PKW job from TB
Details refer to “Function diagrams”, Section 8 Sheets Z110 and Z111
0000 to FFFF H
1
Ind: 12
Type: O2
P052 = 3
n739
(2739)
Display of PKW response to supplementary boards in locations 2 and
3
i001: 1
st
word of PKW job from 1
st
CB
...
i004 4
th
word of PKW job from 1
st
CB
i005: 1
st
word of PKW job from location 2
nd
CB
...
i008 4
th
word of PKW job from 2
nd
CB
i009: 1
st
word of PKW job from TB
...
i012: 4
th
word of PKW job from TB
Details refer to “Function diagrams”, Section 8 Sheets Z110 and Z111
0000 to FFFF H
1
Ind: 12
Type: O2