Align the cable entry support and the cable entry plate to the terminal box enclosure so that
the sealing surface between the terminal box and the terminal box cover form a flat face. There
must be no steps in the sealing area.
6.3.5 Performing connection operations
1. Before closing the terminal box, please check that:
The electrical connections in the terminal box are tight and in full compliance with the
specifications above
The motor is connected so that it rotates in the direction specified
The inside of the terminal box is clean and free of any cable debris, dirt and foreign
bodies.
All gaskets and seals are intact
The pressure relief device is intact Depending on the type of terminal box being used,
the pressure relief device can be implemented either by sealing the slots or by using a
pressure relief diaphragm.
WARNING
Damaged pressure relief device
Water and foreign bodies can penetrate the enclosure if the pressure relief device is
damaged: The degree of protection of the terminal box is no longer guaranteed, a short-
circuit can occur, which can result in death, serious injury or material damage.
Do not operate the machine with a damaged pressure relief device.
Any damage may only be repaired after prior discussion with the person responsible
for the safety of the plant or system and only using original parts.
2. Close the terminal box.
See section "Tightening torques for screw and bolt connections (Page 101)" for the
tightening torque of the fixing bolts for the cover.
6.4 Connecting the auxiliary circuits
6.4.1 Selecting cables
Take the following criteria into account when selecting the connecting cables for the auxiliary
circuits:
Rated current
Rated voltage
System-dependent conditions, such as ambient temperature, routing type, cable cross-
section as defined by required length of cable, etc.
Requirements according to IEC/EN 60204‑1
Electrical connection
6.4 Connecting the auxiliary circuits
SIMOTICS HV C 1NA14544WA600AG0-Z
Operating Instructions 06/2018 57