These consequences are independent of the motor size and quenching principle of the switch
used, i.e. they can also occur when using minimum oil,SF6- or air-blast switches.
Avoid shutting down the machine during startup by, for instance, checking for errors in the
starting control or for excessively sensitive protection settings.
Keep shutdowns during startup for checking the direction of rotation or other tests to an
absolute minimum.
Commissioning
7.5 Overvoltages when switching high-voltage motors
SIMOTICS HV C 1NA14544WA600AG0-Z
64 Operating Instructions 06/2018