Functions
6.11 Operation in fieldbus systems
SINAMICS G110D
174 Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Table 6- 59 Default output process image (master to slave) - Dual slave mode
Bit
Usage
Description
Slave 2
DO0 Motor control bit 0
DO2 DO1 DO0
0 0 0 OFF1
0 0 1 Fixed frequency 1 (default 50 Hz)
0 1 0 Fixed frequency 2 (default -50 Hz)
0 1 1 Fixed frequency 3 (default 10 Hz)
1 0 0 Fixed frequency 4 (default 15 Hz)
1 0 1 Fixed frequency 5 (default 20 Hz)
1 1 0 Fixed frequency 6 (default 25 Hz)
1 1 1 With active trip: Fault ACK (1)
With no Trip: OFF2 (2)
DO1
Motor control bit 1
DO2 Motor control bit 2
DO3 A / B select 0: 'A' slave active
1: 'B' slave active
Slave 1
DO0
Serial clock out
Clock signal for CTT2 data transfer from AS-i master
DO1
Serial data out
Data signal for CTT2 data transfer from AS-i master
DO2 Quickstop override 0: Quick stop active
1: Quick stop override: allow Inverter to ignore quick stop
DO3 A / B select 0: 'A' slave active
1: 'B' slave active
(1) The AS-i specification mandates the simultaneous use of ‘Motor Left’ and ‘Motor Right’ as fault acknowledge, particu-
larly if there is no spare input available for this function.
(2) If no fault is active then simultaneous operation of ‘Motor Left’ and ‘Motor Right’ constitutes a process image error. In
this state both the inverter motor outputs and the motor holding brake outputs are inactive, causing the motor to coast to a
halt and engaging the motor holding brake in exactly the same way as an OFF2 command. This state is maintained until
both ‘Motor Left’ and ‘Motor Right’ are deactivated at the same time.
Table 6- 60 Default input process image (slave to master) - Single slave mode
Bit
Usage
Description
DI0 Ready 0: Inverter is not responsive to AS-i master
1: Inverter is ready to respond to commands from the AS-i master
DI1 Motor active 0: Inverter motor outputs are high impedance
1: Inverter motor outputs are active
DI2 Digital input 1 0: Input 1 is inactive
1: Input 1 is active
DI3 Digital input 2 0: Input 2 is inactive
1: Input 2 is active