Connection to a fieldbus
6.4 Communication via RS485
Inverter with CU240B-2 and CU240E-2 Control Units
138 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
No. Description Comments
106
Request not included / task is not
supported
After request identifier 5,11,12,13,14,15
107 No write access with enabled controller The operating state of the inverter prevents a
parameter change
200/201 Changed minimum/maximum not
achieved or exceeded
The maximum or minimum can be limited
further during operation.
204 The available access authorization does
not cover parameter changes.
Parameter index (IND)
3.(
,1'
3:(
          
VW
ZRUG
QG
ZRUG
UGDQGWK
ZRUG
6XELQGH[,1'3DJHLQGH[
3DUDPHWHUFKDQQHO
Figure 6-15 Structure of the parameter index (IND)
For indexed parameters, select the index of the parameter by transferring the appropriate
value between 0 and 254 to the subindex within a job.
The page index is used to switch over the parameter numbers. Use this byte to add an
offset to the parameter number that is transferred in the 1st word of the parameter
channel (PKE).
Page index: Offset of parameter number
The parameter numbers are assigned to several parameter ranges. The following table
shows which value you must transfer to the page index to achieve a particular parameter
number.
Table 6- 23 Page index setting dependent on parameter range
Page index
Parameter range
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8
Hex value
0000 … 1999 0 0 0 0 0 0 0 0 0x00
2000 … 3999 1 0 0 0 0 0 0 0 0x80
6000 … 7999 1 0 0 1 0 0 0 0 0x90
8000 … 9999 0 0 1 0 0 0 0 0 0x20
10000 … 11999 1 0 1 0 0 0 0 0 0xA0
20000 … 21999 0 1 0 1 0 0 0 0 0x50