Introduction
1.6 Extended scope for adaptation
Inverter with CU240B-2 and CU240E-2 Control Units
22 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
What sources of information do you need to help you set parameters using BICO
technology?
This manual is sufficient for simple signal interconnections, e.g. assigning a different
significance to the to digital inputs.
The parameter list in the List Manual is sufficient for signal interconnections that go
beyond just simple ones.
You can also refer to the function diagrams in the List Manual for complex signal
interconnections.
1.6.2 BICO technology: example
Example: Shifting a basic PLC functionality into the inverter
A conveyor system is to be configured in such a way that it can only start when two signals
are present simultaneously. These could be the following signals, for example:
The oil pump is running (the required pressure level is not reached, however, until after
five seconds)
The protective door is closed
The task is realized by inserting free blocks between the digital input 0 and the internal
ON/OFF1 command and interconnecting them.
p20032 = 5 p20033 = 440
DI 1
DI 0
ON/
OFF1
p0840
Index [0]
r20160
p20159 = 5,0 [s]
p20162 = 430
p20161 = 5
0
T
PDE 0
p20158
Index [0]
r20031
r0722.1
r0722.0
Index [1]
Index [2]1
1
Index [3]
p20030
Index [0]
&
AND 0
Figure 1-4 Example: Signal interconnection for interlock
The signal of digital input 0 (DI 0) is fed through a time block (PDE 0) and is interconnected
with the input of a logic block (AND 0). The signal of digital input 1 (DI 1) is interconnected to
the second input of the logic block. The logic block output issues the ON/OFF1 command to
switch-on the motor.
Table 1- 9 Parameterizing an interlock
Parameter Description
P0700 = 2 Selecting the command source: Digital inputs
P0701 = 0 Enable ("open") digital input 0 (DI 0) for BICO parameterization
P0702 = 0 Enable ("open") digital input 1 (DI 1) for BICO parameterization
P20161 = 5 The time block is enabled by assigning to runtime group 5 (time slice of
128 ms)