Commissioning
4.2 Preparing commissioning
Inverter with CU240B-2 and CU240E-2 Control Units
58 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Motor data / data on the motor rating plate
If you use the STARTER commissioning tool and a SIEMENS motor, you only have to
specify the motor Order No. In all other cases, you must read-off the data from the motor
rating plate and enter into the appropriate parameters.
P0307
3~Mot
1LA7130-4AA10
EN 60034
Cos ϕ 0.81
50 Hz
1455/min
5.5kW 19.7/11.A
230/400 V Δ/Υ
Cos ϕ 0.82
60 Hz
6.5kW
460 V
10.9 A
1755/min
No UD 0013509-0090-0031 TICI F 1325 IP 55 IM B3
Υ 440-480
11.1-11.3 A 45kg
Δ/Υ 220-240/380-420 V
19.7-20.6/11.4-11.9 A
P0311
P0308
P0304P0305
P0310
95.75%
P0309
NOTICE
Information about installation
The rating plate data that you enter must correspond to the connection type of the motor
(star connection [Y]/ delta connection [Δ]), i.e. for a delta motor connection, the delta rating
plate data must be entered.
In which region of the world is the motor used? - Motor standard [P0100]
Europe IEC: 50 Hz [kW] - factory setting
North America NEMA: 60 Hz [hp] or 60 Hz [kW]
What is the prevailing temperature where the motor is operated? [P0625]
Motor ambient temperature [P0625], if it differs from the factory setting = 20° C.