Commissioning
4.3 Commissioning with factory settings
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
61
Table 4- 1 Command and setpoint sources
Parameter Description
P0700 = 2 or 6 Select the command source
2: Digital inputs (P0701 … P0709) (factory setting for CUs without PROFIBUS interface)
6: Fieldbus (P2050 … P2091), (factory setting for CUs with PROFIBUS DP interface)
P1000 = 2 or 6 Select the setpoint source
2: Analog setpoint (factory setting for CUs without PROFIBUS DP interface)
6: Fieldbus (factory setting for CUs with PROFIBUS DP interface)
Table 4- 2 Factory settings of additional important parameters
Parameter Factory setting Meaning of the factory
setting
Name of the parameter and comments
P0010 0 Ready to be entered Drive, commissioning parameter filter
P0100 0 Europe [50 Hz] IEC/NEMA motor standard
IEC, Europe
NEMA, North America
Note: This parameter cannot cannot be changed in FW4.3.
P0300 1 Induction motor Motor type selection (induction motors / synchronous
motor)
P0304 400 [V] Rated motor voltage (in accordance with the rating plate in
V)
P0305 depends on the
Power Module
[A] Rated motor current (in accordance with the rating plate in
A)
P0307 depends on the
Power Module
[kW/hp] Rated motor power (in accordance with the rating plate in
kW/hp)
P0308 0 [cos phi] Rated motor power factor (in accordance with the rating
plate in cos 'phi'). If P0100=1, 2, then P0308 has no
significance.
P0310 50 [Hz] Rated motor frequency (in accordance with the rating plate
in Hz)
P0311 1395 [rpm] Rated motor speed (in accordance with the rating plate in
rpm)
P0335 0 Non-ventilated: Shaft-
mounted fan in the motor
Motor cooling type (specify the motor cooling system)
P0625 20 [°C] Motor ambient temperature
P0640 200 [A] Current limit (of the motor)
P0970 0 Locked Reset drive parameters (restore to the factory settings)
P1080 0 [rpm] Minimum speed
P1082 50 [rpm] Maximum speed
P1120 10 [s] Ramp-function generator, ramp-up time
P1121 10 [s] Ramp-function generator, ramp-down time
P1300 0 V/f control with linear
characteristic
Open-loop/closed-loop control operating mode