Commissioning
4.5 Commissioning with STARTER
Inverter with CU240B-2 and CU240E-2 Control Units
82 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Carry-out basic commissioning
The configuration wizard guides you step by step through the commissioning procedure.
After the basic commissioning, you can change all of the settings and make detailed
changes.
In the start dialog box of the basic commissioning, select the control mode of the motor. If
you are not certain which control mode you require for your application, then initially
select V/f control. Help on how to select the control mode is provided in Chapter Motor
control (Pag
e 168).
Figure 4-8 Basic commissioning with V/f control
With "Continue" you can go to the next dialog boxes where you must make the
appropriate settings for your particular application.
In the "Drive functions" dialog, we recommend the setting "Identify motor data at standstill
and with the motor rotating".
If the motor cannot rotate freely, e.g. where travel is mechanically limited, select the
setting "Identify motor data at standstill".