Connection to a fieldbus
6.3 Communication via PROFIBUS
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
117
Status word 3 (ZSW3)
Status word 3 has the following standard assignment. You can change the assignment with
BICO technology.
Table 6- 12 Status word 3 and interconnection with parameters in the inverter
Bit Valu
e
Significance Description P No.
0 1 DC braking active --
1 1 |n_act| > p1226 Absolute current speed > stationary state detection
2 1 |n_act| > p1080 Absolute actual speed > minimum speed
3 1 i_act ≧ p2170 Actual current ≥ current threshold value
4 1 |n_act| > p2155 Absolute actual speed > speed threshold value 2
5 1 |n_act| ≦ p2155 Absolute actual speed < speed threshold value 2
6 1 |n_act| ≧ r1119 Speed setpoint reached
7 1 DC link voltage ≦ p2172 Actual DC link voltage ≦ threshold value
8 1 DC link voltage > p2172 Actual DC link voltage > threshold value
9 1 Ramping completed Ramp-function generator is not active.
10 1 Technology controller output at lower limit Technology controller output ≦ p2292
11 1 Technology controller output at upper limit Technology controller output > p2291
p2051[3] =
r0053
12 Not used
13 Not used
14 Not used
15 Not used