7.10 Safe Torque Off (STO) safety function
Inverter with CU240B-2 and CU240E-2 Control Units
222 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Set the following in the above screen:
① ② F-DI input filter (debounce time) and monitoring for simultaneous operation
(discrepancy):
The method of functioning of the two filters is described in the section entitled F-DI
sign
al filtering (Page 216).
③ ④ Time in
terval for forced dormant error detection:
Information regarding forced dormant error detection can be found in the Forced
dorm
ant error detection (Page 219) section.
Close the screen.
7.10.7.3 Activate settings
Click "Copy parameters" and then click "Activate settings":
If the password = 0 (factory setting), follow the prompts in order to set a password.
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 220).
Confirm the prompt for saving your settings (copy RAM to ROM).
Switch off the Control Unit power supply for approximately 10 seconds (Power ON
Reset). Only then will your changes become effective.
7.10.7.4 Multiple assignment of the DI
Check whether the digital inputs used as fail-safe input are also assigned a further
function.
NOTICE
Both, the assignment of digital inputs with the selection of a safety function or with a
"standard" function can lead to an unexpected behavior of the motor.