EasyManua.ls Logo

Siemens SINAMICS G120 CU240E-2 - Page 36

Siemens SINAMICS G120 CU240E-2
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
36 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
PM240 Power Dimensions Clearances
IP20 kW Height Width Depth a b c top bottom lateral
mm
inch
499
19,65
275
10,83
204
8,03
405
15,9
235
9,25
11
0,4
300
11,81
300
11,81
0
0
FSE
without
filter
37 … 45
Fixing: M6 screws, Torque: 6 Nm / 53 lbf.in
mm
inch
635
25,00
275
10,83
204
8,03
541
21,30
235
9,25
11
0,4
300
11,81
300
11,81
0
0
FSE with
filter,
Class A
37 … 45
Fixing: M6 screws, Torque: 6 Nm / 53 lbf.in
mm
inch
634
24,96
350
13,78
316
12,44
598
23,54
300
11,81
11
0,4
350
13,78
350
13,78
0
0
FSF
without
filter
55 … 132
Fixing: M8 screws, Torque: 13 Nm / 115 lbf.in
mm
inch
934
36,77
350
13,78
316
12,44
899
35,39
300
11,81
11
0,4
350
13,78
350
13,78
0
0
FSF with
filter,
Class A
55 … 90
Fixing: M8 screws, Torque: 13 Nm / 115 lbf.in
mm
inch
1533
60,35
326
12,9
547
21,5
1506
59,29
125
4,92
14,5
0,57
250
9,84
150
5,91
50/0
1,970
FSGX 160 … 250
Fixing: M8 screws, Torque: 13 Nm / 115 lbf.in
*) up to 40 °C without any lateral clearance

Table of Contents