Functions
5.4 Setpoint sources
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
101
Using BICO technology, you can also assign the JOG function to other keys.
Parameter Description
P0003 = 3 User access level
3: Expert mode
P1055 = ... Enable JOG CW
Possible sources: 722.x (digital inputs) / 19.8 (JOG key on the Operator Panel) /
r2090.8 (serial interface)
P1056 = ... Enable JOG CCW
Possible sources: 722.x (digital inputs) / 19.8 (JOG key on the Operator Panel) /
r2090.9 (serial interface)
5.4.6 Specifying the motor speed via the fieldbus
Specifying the motor speed via the fieldbus
To specify the speed of the motor via the fieldbus, the inverter must be connected to a
higher-level controller via a PC tool. For more information, see "Operation in fieldbus
systems".