Functions
5.11 Operation in fieldbus systems
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
163
21
%LW
%LW
%LW
%LW
%LW
%LW
%LW
ZLWKRXWIXQFWLRQ
352),%86'3
VWDWXV/('
352),%86'3
LQWHUIDFH
352),%86$GGUHVV
',3VZLWFKHV
Figure 5-19 PROFIBUS interface, diagnostics, and address setting on the Control Unit
Set the DIP switch to address 10 (as shown in the following table).
Table 5- 56 Examples of setting the PROFIBUS address
DIP switch 1 2 3 4 5 6 7
The figure specified in this row must be added to
the address.
1 2 4 8 16 32 64
Example 1: Address = 10 = 2 + 8
Example 2: Address = 88 = 8 + 16 + 64
The valid address range is specified in the table below:
Table 5- 57 Valid PROFIBUS addresses
DIP switch settings Meaning
0 PROFIBUS address defined via P0918
1 … 125 Valid PROFIBUS address
126, 127 Invalid PROFIBUS address