EasyManua.ls Logo

Siemens Sinamics G120 CU240S DP - Configuring Converter for PROFINET (Example)

Siemens Sinamics G120 CU240S DP
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.11 Operation in fieldbus systems
Frequency inverter
172 Operating Instructions, 08.10. 2008, t.b.d.
5.11.2.4 Example: configuring the frequency converter on PROFINET
Differences between PROFIBUS and PROFINET
The procedure for operating the frequency inverter on PROFINET differs only slightly from
the above description for PROFIBUS. The following section covers only the key differences
between PROFIBUS and PROFINET.
Hardware components (example)
In comparison to PROFIBUS, the S7 CPU, the Control Unit of the frequency inverter and the
communication cable must be configured for PROFINET.
Component Type Order no. Qty
Central controller
Power supply PS307 2 A 6ES7307-1BA00-0AA0 1
S7 CPU CPU 315-2 PN/DP 6ES7315-2EG10-0AB0 1
Memory card MMC 2MB 6ES7953-8LL11-0AA0 1
DIN rail DIN rail 6ES7390-1AE80-0AA0 1
PROFINET connector PROFINET connector 6GK1901-1BB10-2Ax0 1
PROFINET cable PROFINET cable 6XV1840-2AH10 1
Drive
SINAMICS G120 Control
Unit
CU240S PN 6SL3244-0BA21-1PA0 1
SINAMICS G120 Power
Module
PM240 6SL3224-0BE21-5UA0 1
Basic Operator Panel BOP 6SL3255-0AA00-4BA1 1
Motor Three-phase induction
motor
1LA7060-4AB10 1
PROFINET connector PROFINET connector 6GK1901-1BB10-2Ax0 1
Note
The description provided in this manual uses the hardware listed above. Other similar
products not listed above can also be used.
Software components
Component Type Order no. Qty
SIMATIC STEP 7 V5.4 SP2 6ES7810-4CC07-0YA5 1
Drive ES Basic V5.4 6SW1700-5JA00-4AA0 1

Table of Contents

Related product manuals