EasyManua.ls Logo

Siemens Sinamics G120 CU240S DP - Function Check for Safely Limited Speed (SLS)

Siemens Sinamics G120 CU240S DP
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.12 Safety-related applications
Frequency inverter
210 Operating Instructions, 08.10. 2008, t.b.d.
No. Description Status
7. Check the following points:
No safety fault
r9772.1 = 0 (STO inactive)
r9772.2 = 0 (SS1 deselected)
r9772.14 = 0
8. Check whether the motor involved rotates. If yes, check the following points:
The cabling between the Control Unit and Power Module is correct
Correct assignment, drive No. - frequency inverter - Power Module -
motor
The hardware can function correctly
Correct wiring of the shutdown paths
Correct STO terminal assignment at the Control Unit
Correct parameterization of the SS1 function
Function check, "Safely Limited Speed" (SLS)
This check involves the following steps:
Table 5- 75 Function, "Safely Limited Speed" (SLS)
No. Description Status
1. Initial state
The frequency inverter signals "ready for switching on" (P0010 = 0)
No safety faults and alarms
r9772.4 = r9772.5 = 0 (SLS deselected and inactive)
2. Switch on the motor. The motor speed must be higher than the parameterized
safely limited speed, if the machine permits this
3. Check whether the motor involved rotates
4. Select SLS while the ON command is being issued
5. Check the following points:
r9772.4 = 1 (SLS selected)
The motor response depends on the selected mode of the SLS function
SLS mode 0
The drive speed decreases corresponding to the selected ramp time
and then the frequency inverter is subsequently passivated
SLS mode 1
The motor speed decelerates corresponding to the selected ramp
time. The motor then rotates with the parameterized safely limited
speed
SLS mode 2
The frequency inverter is immediately passivated, the motor coasts
down
SLS mode 3
The frequency inverter is immediately passivated, the motor coasts
down
r9772.5 = 1 (SLS active)
6. Deselect SLS

Table of Contents

Related product manuals