Technical data
8.2 Technical data of the CU240E
Frequency inverter
224 Operating Instructions, 08.10. 2008, t.b.d.
8.2 Technical data of the CU240E
CU240E
Feature Data
Operating voltage Supply from the Power Module
Heat loss < 40W
Setpoint resolution 0.01 Hz
Digital inputs
(dependent on the CU
type)
6, floating; PNP/NPN switchable
Low < 5 V, High > 10 V, maximum input voltage 30 V, 5.5 mA
Analog inputs 2, with 10-bit resolution
AI0: 0 V to 10 V, 0 mA to 20 mA and -10 V to+10 V
AI1: 0 V to 10 V and 0 mA to 20 mA
Both analog inputs can also be configured as digital inputs
Digital outputs 3 relay outputs, 30 V DC / max. 0.5 A for a resistive load
Analog outputs 2
AO0: 0 V to 10 V or 0 mA to 20 mA
AO1: 0 mA to 20 mA
Weight 0.21 kg

Table of Contents