Loading...
Connection
3.3 Mounting Power Modules
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
31
3.3.1 Dimensions, hole drilling templates, minimum clearances, tightening torques
Overview of dimensions and hole drilling templates for the Power Modules
0.37 kW … 1.5 kW 2,2 kW … 4 kW 7,5 kW … 15 kW
Retaining type
2 x M4 bolts
2 x M4 nuts
2 x M4 washers
Retaining type
4 x M4 bolts
4 x M4 nuts
4 x M4 washers
Retaining type
4 x M5 bolts
4 x M5 nuts
4 x M5 washers
Tightening torques
2.5 Nm (22.1 lbf.in)
Tightening torques
2.5 Nm (22.1 lbf.in)
Tightening torques
2.5 Nm (22.1 lbf.in)
Distances from other devices
Lateral: 30 mm (1.18 inch)
Top/bottom: 100 mm (3.93 inch)
Distances from other devices
Lateral: 40 mm (1.57 inch)
Top/bottom: 100 mm (3.93 inch)
Distances from other devices
Lateral: 50 mm (1.96 inch)
Top/bottom: 125 mm (4.92 inch)
Depth
Standalone: 145 mm (5.71 inch)
With CU240E: 187 mm (7.36 inch)
With CU240S: 208 mm (8.19 inch)
Depth
Standalone: 165 mm (6.50 inch)
With CU240E: 207 mm (8.15 inch)
With CU240S: 228 mm (8.98 inch)
Depth
Standalone: 185 mm (7.28 inch)
With CU240E: 227 mm (8.94 inch)
With CU240S: 248 mm (9.76 inch)

Table of Contents