EasyManua.ls Logo

Siemens Sinamics G120 CU240S DP - Initial Coupling of the CU and PM - Message F0395

Siemens Sinamics G120 CU240S DP
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
4.1 Initial coupling of the CU and PM - message F0395
Frequency inverter
46 Operating Instructions, 08.10. 2008, t.b.d.
4.1 Initial coupling of the CU and PM - message F0395
Description
Message "F0395" is displayed when Control Units or Power Modules are switched on for the
first time or after they have been replaced.
This message monitors the two inverter components (CU and PM) to ensure that they are
not replaced without authorization. Make sure that the parameter set on the Control Unit is
compatible with the Power Module and the application before acknowledging message
'F0395' as described below.
When you acknowledge F0395, you accept the parameter set on the Control Unit.
Acknowledging message F0395
Depending on which command source is set, you can acknowledge message F0395 in the
following ways:
If the command source is "BOP": press function key FN
If the command source is 'Terminals' (P0700 = 2): digital input 2 (factory setting for the
acknowledge command)
If the command source is 'Fieldbus' (P0700 = 6): control word 1 (STW1 / bit 7)
Message F0395 is also acknowledged when 'Restoring the factory settings'.

Table of Contents

Related product manuals