Commissioning
4.4 Commissioning with factory settings
Frequency inverter
56 Operating Instructions, 08.10. 2008, t.b.d.
4.4.3 Default terminal settings
Factory settings of the process interfaces
Digital inputs
Terminal Abbreviation Parameter Factory setting Meaning of the factory setting
5 DI0 P0701 1 ON / OFF1
6 DI1 P0702 12 Direction reversal
7 DI2 P0703 9 Error acknowledgment
8 DI3 P0704 15 Fixed setpoint selector bit 0 (direct) [P1001]
16 DI4 P0705 16 Fixed setpoint selector bit 1 (direct) [P1002]
17 DI5 P0706 17 Fixed setpoint selector bit 2 (direct) [P1003]
40 DI6 P0707 18 Fixed setpoint selector bit 3 (direct) [P1004]
41 DI7 P0708 0 Digital input blocked
42 DI8 P0709 0 Digital input blocked
Digital inputs of the safety functions
Terminal Abbreviation Parameter Factory setting Meaning of the factory setting
60 FDI0A
61 FDI0B
62 FDI1A
63 FDI1B
P9603 0 Digital inputs of the safety functions are blocked
Digital outputs (relay outputs)
Terminal Abbreviation Parameter Factory setting Meaning of the factory setting
18 NC
19 NO
20 COM
DO0 P0731 52.3 Drive fault active
21 NO
22 COM
DO1 P0732 52.7 Drive alarm active
23 NC
24 NO
25 COM
DO2 P0733 0.0 Relay output is blocked