Commissioning
4.6 Commissioning with the operator panel
Frequency inverter
72 Operating Instructions, 08.10. 2008, t.b.d.
4.6.2 BOP controls and displays
How to use the BOP
Key Function Function / result
Status LED Shows parameter numbers, values, and physical units of
measure.
Parameter access This button allows you to access the parameter list.
r _ _ _ _ read-only parameters: for display only
P_ _ _ _ write parameters: these can be changed
Increase displayed
values
This button allows you to scroll forwards in the parameter
list;
Decrease displayed
values
This button allows you to scroll backwards in the parmeter
list.
Function key The function of this button varies depending on the data
displayed:
If a parameter number is displayed and you press this
button once briefly, you can return to the start of the
parameter list r0000.
If a parameter value is displayed and you press this
button once briefly, the cursor jumps to the next position
(e.g. in a multi-digit number). This allows you to change a
decimal number digit by digit, for example.
If an alarm or a fault message is displayed and you press
this button once briefly, this acknowledges the message.
Start motor Press this button to start the motor.
In the factory setting, this button is not active.
To activate it, set P0700 = 1.
Stop motor Press this button to stop the motor.
OFF2 is always activated: Press twice briefly or press
once for longer: The motor coasts to a standstill.
In the factory setting, OFF1 is not active.
To activate it, set P0700 = 1.
Change direction of
rotation
When you press this button, the direction of motor rotation
is reversed (CW/CCW).
In the factory setting, this button is not active.
To activate it, set P0700 = 1.
Jog mode Run the motor in jog mode. The motor rotates at a
predefined speed for as long as this key is pressed (and
kept down).
In the factory setting, this button is not active.
To activate it, set P0700 = 1.