5.2.5 Three-wire control, method 1
Function description
The first control command is a permanent enable signal for starting the motor. When this
enable signal is canceled, the motor stops.
CW rotation is activated with the positive edge of the second control command.
CCW rotation is activated with the positive edge of the third control command.
R
R
R
(QDEOH
VLJQDO
0RWRU21
&:
0RWRU21
&&:
0RWRU
VSHHG
&RPPDQGLJQRUHG
$FWLYH
$FWLYH$FWLYH
2))
W
Figure 5-5 Three-wire control using digital inputs, method 1
Table 5- 8 Function table
Enable
signal
Motor ON /
CW
Motor ON /
CCW
Function
0 Not
relevant
Not
relevant
OFF1: The motor decelerates to a standstill
1 0→1 0 The motor accelerates to the setpoint
1 0 0→1 The motor accelerates to the inverted setpoint
1 0 0 No effect on the direction of rotation.
1 1 1 OFF1: The motor decelerates to a standstill