Commissioning
4.2 Connecting the inverter to the fieldbus
CU250S-2 Control Units
Compact Operating Instructions, 05/2014, A5E32899990B AB
21
5
The output of the ramp-function generator stops at the actual value.
The output of the ramp-function generator follows the setpoint.
6 0 = Inhibit setpoint The inverter brakes the motor with the ramp-down time p1121 of the ramp-function
Motor accelerates with the ramp-up time p1120 to the setpoint.
7 0 → 1 = Acknowledge faults Acknowledge fault. If the ON command is still active, the inverter switches
to"closing lockout" state.
10
The inverter ignores the process data from the fieldbus.
Control via fieldbus, the inverter accepts the process data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the motorized potentiometer.
Reduce the setpoint saved in the motorized potentiometer.
15 Reserved Changes over between settings for different operation interfaces (command data
Power supply switched on; electronics initialized; pulses locked.
1 1 = Ready Motor is switched on (ON/OFF1 = 1), no fault is active. With the command "Enable
operation" (STW1.3), the inverter switches on the motor.
Motor follows setpoint. See control word 1, bit 3.
The inverter has a fault. Acknowledge fault using STW1.7.
Coast down to standstill is not active.
Quick stop is not active.
1 = Closing lockout active
It is only possible to switch on the motor after an OFF1 followed by ON.
Motor remains switched on; no acknowledgement is necessary.
8 1 = Speed deviation within the
Setpoint / actual value deviation within the tolerance range.
1 = Master control requested
The automation system is requested to accept the inverter control.
10 1 = Comparison speed reached
Speed is greater than or equal to the corresponding maximum speed.
Comparison value for current or torque has been reached or exceeded.
Signal to open and close a motor holding brake.
13 0 = Alarm, motor
--
14
1 = Motor rotates clockwise
Internal inverter actual value > 0
0 = Motor rotates
Internal inverter actual value < 0
15 0 = Alarm, inverter thermal