Parameters
List of Parameters
1-100
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines source of pulse enable/disable signal.
Dependency: Active only when P0719 = 0 (Auto selection of command/setpoint source).
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Description: Defines source of pulse enable/disable signal.
Dependency: Active only when P0719 = 0 (Auto selection of command/setpoint source).
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Description: Defines source of pulse enable/disable signal.
Dependency: Active only when P0719 = 0 (Auto selection of command/setpoint source).
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Description: Defines PROFIBUS address.
There are two ways to set the bus address:
1. via DIP switches on the control unit
2. via a user-entered value
Note: Possible PROFIBUS settings:
1 ... 125
0, 126, 127 are not allowed
The following applies when PROFIBUS is used:
All PROFIBUS DIP switches = OFF --> Address defined in P0918 is valid otherwise the DIP switch setting has pri-
ority and P0918 indicates DIP switch setting.
p0852[0...2] BI: Pulse enable / Pulse enable
CU240E
CU240S
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 1
p0852[0...2] BI: Pulse enable / Pulse enable
CU240S DP
CU240S DP-F
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 2090.3
p0852[0...2] BI: Pulse enable / Pulse enable
CU240S PN Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 8890.3
p0918 PROFIBUS address / PROFIBUS address
CU240S DP
CU240S DP-F
Access level: 2 P-Group: Communications Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: T
Min Max Factory setting
1 125 3