List of Parameters
Parameters
1-115
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines fixed frequency setpoint 1.
There are 2 types of fixed frequencies:
1. Direct selection (P1016 = 1):
- In this mode of operation 1 Fixed Frequency selector (P1020...P1023) selects 1 fixed frequency.
- If several inputs are active together, the selected frequencies are summed.
E.g.: FF1 + FF2 + FF3 + FF4.
2. Binary coded selection (P1016 = 2):
- Up to 16 different fixed frequency values can be selected using this method.
- The fixed frequencies are selected according to FP3210.
Dependency: Select fixed frequency operation (using P1000).
Inverter requires ON command to start in the case of direct selection. Therefore r1025 must be connected to P0840
to start.
Note: Fixed frequencies can be selected using the digital inputs.
Description: Defines fixed frequency setpoint 2.
Note: See parameter P1001 (fixed frequency 1).
Description: Defines fixed frequency setpoint 3.
Note: See parameter P1001 (fixed frequency 1).
Description: Defines fixed frequency setpoint 4.
Note: See parameter P1001 (fixed frequency 1).
p1001[0...2] Fixed frequency 1 / Fixed frequency 1
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 0.00 [Hz]
p1002[0...2] Fixed frequency 2 / Fixed frequency 2
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 5.00 [Hz]
p1003[0...2] Fixed frequency 3 / Fixed frequency 3
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 10.00 [Hz]
p1004[0...2] Fixed frequency 4 / Fixed frequency 4
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-650.00 [Hz] 650.00 [Hz] 15.00 [Hz]