List of Parameters
Parameters
1-129
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint.
The value set here is valid for both clockwise and anticlockwise rotation. Futhermore, the monitoring function |f_act|
>= P1082 (r0052 Bit10, see example below) is affected by this parameter.
Example:
Dependency:
The maximum value of P1082 also depends on the nominal frequency: Max. P1082 = min(15*P0310, 650 Hz).
As consequence P1082 can be affected if P0310 is changed to a smaller value.
The maximum frequency and the pulse frequency depending on each other. The maximum frequency affects the
pulse frequency according to the following table.
Example:
If P1082 is set to 350 Hz a pulse frequency from at least 6 kHz is necessary. If P1800 is smaller than 6 kHz the
parameter is changed P1800 = 6 kHz.
The maximum output frequency of inverter can be exceeded if one of the following is active:
The resultant value is displayed in r1084 (resultant maximum frequency).
p1082[0...2] Max. frequency / Max. frequency
CU240E
CU240S
Access level: 1 P-Group: Setpoints Data type: Floating Point
Quick comm. YES Active: NO Data set: DDS
Can be changed: C, T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 50.00 [Hz]
0 t
1
t
f_act
r0052
Bit 10
|f_act| p1082 (f_max)
p1082
p1082 - p2162
2 kHz
0 - 133.3 Hz
f
max
p1082
4 kHz
0 - 266.6 Hz
6 kHz
0 - 400 Hz
8 - 16 kHz
0 - 650 Hz
p1800
(Flying restart active) :
(Slip compensation active) :
p0310
100
r0330
100
p1336
p1082 ff(p1335)f
max,slipmaxmax
+=+=
- p1335
0
- p1200
0
p0310
100
r0330
2p1082 f2f(p1200)f
nom,slipmaxmax
+=+=