List of Parameters
Parameters
1-133
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines skip frequency 4 which avoids effects of mechanical resonance and suppresses frequencies within +/-
P1101 (skip frequency bandwidth).
Note: See P1091 (skip frequency 1).
Description: Delivers frequency bandwidth to be applied to skip frequencies (in [Hz]).
Note: See P1091 (skip frequency 1).
Description: This parameter suppresses negative setpoints. Therefore, modification of the motor direction is inhibited to the set-
point channel.
If a min. frequency (P1080) and a negative setpoint are given, the motor is accelerated by a positive value in rela-
tionship to the min. frequency.
Description: Defines source of reverse command used when P0719 = 0 (Auto selection of command/setpoint source).
Description: Defines source of reverse command used when P0719 = 0 (Auto selection of command/setpoint source).
p1094[0...2] Skip frequency 4 / Skip frequency 4
Access level: 3 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 0.00 [Hz]
p1101[0...2] Skip frequency bandwidth / Skipfreq bandwidth
Access level: 3 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [Hz] 10.00 [Hz] 2.00 [Hz]
p1110[0...2] BI: Inhibit neg. freq. setpoint / Inh. neg. setp
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 0
p1113[0...2] BI: Reverse / Reverse
CU240E
CU240S
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 722.1
p1113[0...2] BI: Reverse / Reverse
CU240S DP
CU240S DP-F
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 2090.11