List of Parameters
Parameters
1-137
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines ramp-down time from maximum frequency to standstill for OFF3 command.
Note: This time may be exceeded if the VDC_max. level is reached.
Description: Defines command source of RFG enable command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output will be set immediately to 0.
Dependency: When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
Description: Defines command source of RFG enable command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output will be set immediately to 0.
Dependency: When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
Description: Defines command source of RFG enable command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output will be set immediately to 0.
Dependency: When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
Description: Defines command source of RFG start command (RFG: ramp function generator).
If binary input is equal to zero then the RFG output is held at its present value.
Dependency: When Standard Telegram selected (P0700 = 6, P0922 = Standard Telegram), parameter cannot be changed.
p1135[0...2] OFF3 ramp-down time / OFF3 ramp-dwn time
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. YES Active: NO Data set: DDS
Can be changed: C, U, T
Min Max Factory setting
0.00 [s] 650.00 [s] 5.00 [s]
p1140[0...2] BI: RFG enable / RFG enable
CU240E
CU240S
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 1
p1140[0...2] BI: RFG enable / RFG enable
CU240S DP
CU240S DP-F
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 2090.4
p1140[0...2] BI: RFG enable / RFG enable
CU240S PN Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 8890.4
p1141[0...2] BI: RFG start / RFG start
CU240E
CU240S
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 1