Parameters
List of Parameters
1-142
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Specifies number of times inverter will attempt to restart if automatic restart P1210 is activated.
Description: Enables/disables holding brake function.
The mechanical motor holding brake (MHB) is controlled via the signal of status word 1 r0052 Bit12 "Brake open".
This signal can be issued via:
status word of the serial interface (e.g. USS)
digitial outputs (e.g. DO0: ==> P0731 = 52.C (r0052 Bit12))
Values: 0: Motor holding brake disabled
1: Motor holding brake enabled
Caution: It is not permissible to use the motor holding brake as working brake, as it is generally only designed for a limited
number of emergeny braking operations.
Note: In V/f control (P1300 < 20) a typical value of min. frequency P1080 for motor holding brake is the slip frequency of
the motor r0330.
In a vector control mode (P1300 = 20) the following should be valid:
The value of the min. Frequency P1080 should be zero.
The delay speed loss reaction should be > brake holding times (i.e. P0494 > P1216 and P0494 > P1217 )
The delay time for motor pulled out should be > brake holding times (i.e. P2178 > P1216 and P2178 > P1217 )
Otherwise there may be encoder loss trips (F0090) when the brake is applied and pulses are enabled.
Description: Enables/disables holding brake function.
The mechanical motor holding brake (MHB) is controlled via the signal of status word 1 r0052 Bit12 "Brake open".
This signal can be issued via:
status word of the serial interface (e.g. USS)
digitial outputs (e.g. DO0: ==> P0731 = 52.C (r0052 Bit12))
Values: 0: Motor holding brake disabled
1: Motor holding brake enabled
p1211 Number of restart attempts / Restart attempts
Access level: 3 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: C, U, T
Min Max Factory setting
0 10 3
p1215 Holding brake enable / MHB enable
CU240E Access level: 2 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: C, T
Min Max Factory setting
0 1 0
n
nsy
nnsy
Slip
f
n
n n
P0310
100
r0330
[Hz]f
==
p1215 Holding brake enable / MHB enable
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Access level: 2 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: C, T
Min Max Factory setting
0 1 0